Table of Contents
- 1. What Is ISO 11799?
- 2. Where the Temperature and RH Figures Actually Sit
- 3. What the Standard Covers — and What It Doesn't
- 4. Climate Requirements: Temperature, Humidity, and Stability
- 5. Citable Temperature and RH Bands by Collection and Source
- 6. Why the Daily Swing (ΔRH/24 h) Matters More Than the Set Point
- 7. Air Quality: Particulates and Gaseous Pollutants
- 8. Fire Protection, Shelving, and Building Requirements
- 9. How to Demonstrate Compliance
- 10. What to Ask a Supplier Before You Write Them Into the Specification
1. What Is ISO 11799?
ISO 11799 "Information and documentation — Document storage requirements for archive and library materials" is the international standard that defines the environmental conditions, building requirements, and operational practices for long-term preservation of paper-based collections. It was developed by ISO Technical Committee 46 (Information and Documentation) and is recognized globally as the benchmark for archive facility design. The current edition is ISO 11799:2024, published in September 2024 as the third edition; ISO 11799:2015 is the second edition and the version most specifications on the market still quote. This article references both, and section 2 explains the difference that matters.
The standard covers the entire storage lifecycle: building construction, fire protection, shelving, climate control (temperature and humidity), air quality (both particulate and gaseous pollutants), lighting, pest management, and disaster preparedness. It is not a certification — there is no "ISO 11799 certified" label — but it serves as the reference specification that funding bodies, government agencies, and professional conservators use to evaluate whether a facility meets acceptable preservation standards.
2. Where the Temperature and RH Figures Actually Sit
This is the most useful thing to get right before you write an environmental section. ISO 11799 does publish temperature and relative humidity guidance — but it does not put those figures in its normative clauses. They sit in an informative annex. In ISO 11799:2024 that is Annex B (informative), Recommended climatic conditions for the long-term storage of archive and library materials, with Annex C (informative), Environmental transitions for materials alongside it; in ISO 11799:2015 the climate figures were in Annex C. Informative means guidance, not requirement.
ISO 11799:2024 replaced the 2015 edition
The third edition was published in September 2024 and replaces ISO 11799:2015 (second edition, December 2015). Its scope covers the siting, construction, and renovation of the storage facility, and the installation and equipment used within and around the building; it applies to repositories where mixed media are stored alongside paper-based materials. Exhibition conditions remain out of scope. Everything the rest of this article says about climate, air quality, fire protection, shelving, and monitoring still holds for the 2024 edition — what changed is where the figures sit and which clauses carry them.
| ISO 11799:2015 (2nd edition) | ISO 11799:2024 (3rd edition, current) | |
|---|---|---|
| Published | December 2015 | September 2024 |
| Climatic figures | Annex C (informative) | Annex B (informative) |
| Environmental transitions | Not a named annex | Annex C (informative), "Environmental transitions for materials" |
| Air pollutants | Annex D (informative), "Guidance for air pollutants" | No dedicated air-pollutant annex in the published contents |
| Monitoring | No numbered sampling clause published | Clause 8, "Environmental monitoring", including 8.2.3 "Deployment and sample rates" and 8.2.4 "Data retention and analysis" |
Two pieces of evidence are worth keeping to hand. The 2015 edition's own introduction carried the disclaimer that "figures and quantities given in this International Standard are intended for general international guidance", and the National Diet Library's review of the revision confirms that, as in the previous two editions, the specific temperature and humidity requirements are given not in the normative body but as informative annexes. A peer-reviewed survey likewise records ISO 11799:2015 as not explicitly specifying recommended temperature and RH ranges.
If a supplier quotes a figure that looks unusually specific, check its vintage. The withdrawn 2003 edition is the origin of several pairs still in circulation — for example 2–18 °C ±1 °C and 30–45% RH ±3% for optimum preservation, or 14–18 °C ±1 °C and 35–50% RH ±3% for staffed stack areas. Those come from a peer-reviewed tabulation of the withdrawn edition, not from the current standard text, so ask which edition a number came from and whether it is normative.
3. What the Standard Covers — and What It Doesn't
ISO 11799:2015 addresses nine major areas:
- Building construction and location — site selection, flood risk, building envelope integrity
- Fire protection — detection, suppression, compartmentation
- Climate control — temperature, relative humidity, stability requirements
- Air quality — particulate filtration, gaseous pollutant limits
- Lighting — maximum illuminance, UV content limits, exposure duration management
- Shelving and storage equipment — materials, spacing, load ratings
- Pest management — integrated pest management (IPM) protocols
- Disaster preparedness — emergency response planning, salvage procedures
- Security and access control
It does NOT cover: exhibition conditions (see separate standards), digitization workflows, cataloging metadata, or the content of preservation policies. It is specifically about the storage environment.
4. Climate Requirements: Temperature, Humidity, and Stability
This is the core of ISO 11799 and the section most relevant to dehumidifier selection. The figures below are the ones the standard's informative annex publishes for long-term storage of paper-based collections. They are guidance, and they are the numbers most often misquoted as clauses — the table therefore names the annex instead of the standard.
| Parameter | Figure published in the informative annex | Practical Interpretation |
|---|---|---|
| Temperature | 14–22°C | Lower is always better for chemical stability. Archives aiming for permanent preservation should target 14–16°C. 18°C is a practical compromise for frequently accessed collections. |
| Relative Humidity | 35–60% | The sweet spot is 45–55% for paper. Below 35% causes brittleness; above 60% accelerates acid hydrolysis and enables mold germination. |
| Short-term Stability | ±5% RH, ±2°C | Widely repeated as "per 24 hours", but the standard does not state that time basis — and no universal daily delta exists across the frameworks. See section 6 for what each document actually says. |
| Long-term Stability | Seasonal adjustment permitted but must be gradual | If seasonal setpoint changes are used (e.g., 50% RH summer, 40% RH winter), the transition must occur over weeks, not days. ISO 11799:2024 puts this in Annex C, "Environmental transitions for materials". |
For photographic materials and magnetic media, ISO 11799 references supplementary standards (ISO 18911, ISO 18923, ISO 18934) that specify more stringent cold storage requirements — down to 4°C for color film and -18°C for cellulose acetate negatives. Note also that the annex itself sits behind a paywall: the figures above circulate because national guidance and vendor literature reproduce them, which is exactly why section 5 cites documents you can actually put in a contract.
5. Citable Temperature and RH Bands by Collection and Source
When you need a number that can survive a dispute, take it from a document that states it normatively — or that labels itself as guidance — and cite that document in the specification. The bands below are the publicly citable ones. The last column matters as much as the numbers: two rows can look identical and carry completely different weight.
| Collection / space | Temperature | Relative humidity | Fluctuation limit and time basis | Source and normative status |
|---|---|---|---|---|
| Paper and textual records, low-sensitivity artifacts, mixed media storage rooms | 50–65 °F (10–18 °C) | 30–50% | Band only; fluctuation between the upper and lower limits is acceptable. No daily delta stated. | NARA 1571, Supplement 2, Table 1 (effective 17 January 2023) — normative for US federal records |
| Artifacts of medium sensitivity | 50–65 °F (10–18 °C) | 40–50% | Band only; no daily delta stated. | NARA 1571, Supplement 2, Table 1 — normative for US federal records |
| Holdings work rooms, storage, and exhibit galleries | 50–75 °F (10–24 °C) | 30–55% | Band only; no daily delta stated. | NARA 1571, Supplement 2, Table 1 — normative for US federal records |
| Photographs, film, and negatives (cold and frozen storage) | Cold store 35 °F (1.7 °C), not below 32 °F; frozen store below 30 °F (−1.1 °C), not above 32 °F | 30–40% | Band only; no daily delta stated. | NARA 1571, Supplement 2, Table 1 — normative for US federal records; ISO 11799 points to ISO 18911 / ISO 18923 / ISO 18934 for the cold-storage side — informative |
| Mixed archives | 13–23 °C, annual average below 18 °C | 35–60% | A "±5%" figure circulates with no stated time base; one UK operator states ≤1 °C in any 24 hours and no daily RH delta. | BS 4971:2017 — national standard, but figures here from secondary sources: verify against the standard text |
| Parchment, vellum, and leather bindings | No publicly citable set point located | No publicly citable figure located; the paper band is often assumed but not verified for these materials | Not stated. | ISO 11799:2024 Annex B / 2015 Annex C — informative and paywalled; EN 16893:2018 handles these materials as relative risk rather than set points — informative |
| Heritage collections generally (paper, parchment, composites) | Relative-risk tables only; no set points | Relative-risk tables only; no set points | Risk expressed as damage from hydrolysis, not as a fluctuation limit. | EN 16893:2018, informative Annexes B and C — guidance, not prescriptive |
| Museums, galleries, libraries, archives (CCI / ASHRAE classes) | 15–25 °C; Class C within 25–75% RH year-round; Class D RH below 75% | Set point 50% RH, or the historic annual average | AA: ±5% RH / ±2 °C short-term. A: as AA plus seasonal ±10% RH. B: ±10% RH / ±5 °C short-term. | CCI Table 2, attributed to S. Michalski for the ASHRAE Handbook — guidance |
| Paintings on canvas or wood | 16–25 °C | 40–60% safest; 50% central value | Level A ±10% RH or seasonal ±5% RH; Level B seasonal ±10% RH, short-term ±10% RH. | CCI Notes 10/4 — guidance |
| Cold or cool store for chemically unstable collections | −20 °C / 10 °C | 40% RH (±10% RH) / 30–50% RH | ±2 °C short-term at −20 °C. | CCI Table 2, as above — guidance |
| Paper, local adoption (Hong Kong Government Records Service) | 18 °C average, maximum ±1 °C in 24 h | 50% average | ±2% RH in 24 hours | GRS Hong Kong, adopted with regard to EN 16893:2018 and BS 4971:2017 — local regulatory adoption |
| Danish State Archives (vendor case study) | 14–18 °C constant | 30–50% year-round | Maximum accepted variation 3% per day. | Munters case study, vendor-authored — verify |
ISO 11799 itself gets no numeric row: its temperature and RH values sit in the informative annex behind a paywall, which is precisely why the standard cannot be quoted as a set point. The BS 4971:2017 and CCI/ASHRAE figures rest on secondary reporting and should be checked against the standard text before they enter a specification. NARA publishes its bands in °F, so they are quoted as published rather than converted where the source gives both, and the CCI/ASHRAE row is a class system rather than a single band — state both the class letter and its fluctuation limit or the number means nothing.
6. Why the Daily Swing (ΔRH/24 h) Matters More Than the Set Point
Two rooms can both sit at 50% RH and carry completely different preservation risk: one holds 50% ±2%, the other swings 50% ±15% twice a day. Most frameworks therefore express climate as a band plus a short-term fluctuation limit — and then treat the daily delta as a separate question, or decline to state one at all.
NARA 1571:2023 is explicit: fluctuation between the upper and lower limits of its Table 1 is acceptable, and seasonal drift — slow changes in targeted indoor temperature that track outdoor temperatures — is permitted for energy efficiency, with the observation that holding a storage room "to maintain a flat line condition has no preservation benefit". ASHRAE and CCI use classes that separate short-term fluctuation (±5% or ±10% RH) from seasonal movement. EN 16893:2018 presents temperature and RH as relative risk of damage, as a function of a material's sensitivity to hydrolysis, rather than as set points.
ΔRH does not mean the same thing in every document
- NARA 1571 (2023): upper and lower limits, acceptable fluctuation between them, and permitted seasonal drift. No daily delta is stated.
- ASHRAE / CCI classes: short-term fluctuation stated separately from seasonal change; the averaging window is part of the class definition, not an afterthought.
- PD 5454:2012 (superseded by BS 4971:2017): reported as no more than 2 °C or 5% RH in a day — the likely origin of most "±5% per day" claims in circulation.
- BS 4971:2017: a "±5%" figure circulates with no stated time basis. Do not present it as a daily limit without checking the standard text.
- Hong Kong Government Records Service: ±1 °C and ±2% RH per 24 hours for paper — one of the few explicit 24-hour deltas published.
- Danish State Archives (vendor case study): maximum accepted variation of 3% per day at 30–50% RH year-round.
Nothing reviewed for this article supports a universal "±X% RH per day" rule. If a specification contains one, ask which document it came from and what averaging period it assumes.
Why the swing is what actually damages collections
- Damage scales with swing size and object sensitivity. CCI publishes a matrix in which ±5% RH produces no damage in low-sensitivity objects but damage in very-high-sensitivity objects, while ±10% RH ranges from none to small-to-severe damage depending on sensitivity class, widening further at ±20% and ±40%. CCI's concept of "proofed fluctuation" is the practical version of this: most objects have already experienced at least ±20% RH, so the question is not whether a swing occurred but whether the object was repaired to tolerate it.
- Damp conditions set a hard ceiling. CCI treats 75% RH as the practical damp boundary, with mold onset of roughly 100 days at 70% RH, 10 days at 80% RH, and 2 days at 90–100% RH.
- US records-storage regulation requires paper-based permanent records to be stored with 24-hour/365-day air conditioning equivalent to office space, referencing ANSI/ASHRAE Standard 55 and ASHRAE Standard 62, and identifies RH above 70%, heat combined with RH above 55%, and poor air circulation as contributors to active mold growth.
The practical consequence for a specification: state a permitted band, a fluctuation limit with its stated averaging period and measurement interval, an agreed seasonal drift allowance, and an absolute ceiling — for most mixed collections well below 70% RH — that triggers alarm and failsafe action on the equipment. A set point alone is not a requirement; it is a number waiting to be argued about at handover.
7. Air Quality: Particulates and Gaseous Pollutants
ISO 11799 addresses air quality in two categories:
Particulate Matter (Dust)
The standard specifies that storage areas should maintain particulate concentrations consistent with ISO 14644-1 Class 8 or better (roughly equivalent to a clean office environment). In practice, this means HEPA filtration — minimum H10 grade, with H12–H13 recommended for collections including photographs, textiles, or fragile paper.
Gaseous Pollutants
This is the part most facilities overlook. ISO 11799 explicitly identifies three categories of gaseous contaminants:
- External pollutants: SO2 (<10 µg/m³), NO2 (<10 µg/m³), O3 (<5 µg/m³)
- Internal pollutants: Acetic acid, formic acid, formaldehyde — generated by wood shelving, adhesives, floor coverings, and the collections themselves
- Removal strategies: Activated carbon adsorption, gas-phase chemisorption media, or desiccant rotor absorption
The standard does not mandate a specific technology, but performance verification requires demonstrating that pollutant concentrations are kept below the specified thresholds. For facilities in urban or industrial areas, this effectively requires active gas-phase filtration.
The ISO figures above come from the air-pollutant guidance in the 2015 edition (Annex D, informative). The published contents of the 2024 edition show no dedicated air-pollutant annex, so if you need pollutant limits that carry regulatory weight, cite NARA 1571 instead. Its Supplement 2, Table 2 sets maximum concentrations after filtration, with tighter limits inside exhibit cases and microclimates:
| Pollutant (after filtration) | Holdings storage rooms | Exhibit cases and microclimates | Source and normative status |
|---|---|---|---|
| Sulfur dioxide (SO2) | 5 µg/m³ (1.9 ppb) | 2.7 µg/m³ (1 ppb) | NARA 1571, Supplement 2, Table 2 — normative for US federal records |
| Nitrogen dioxide (NO2) | 5 µg/m³ (2.6 ppb) | — | NARA 1571, Supplement 2, Table 2 — normative |
| Ozone (O3) | 5 µg/m³ (2.5 ppb) | — | NARA 1571, Supplement 2, Table 2 — normative |
| Acetic acid | 250 µg/m³ (100 ppb), the level indicating severely deteriorating acetate film | 10.0 µg/m³ (4.0 ppb) | NARA 1571, Supplement 2, Table 2 — normative |
| Formaldehyde | — | 5.0 µg/m³ (4.0 ppb) | NARA 1571, Supplement 2, Table 2 — normative |
NARA 1571 also requires gas-phase and particulate filtration in any air handling unit serving holdings storage spaces, on both return and make-up air, with the gas-phase filter ahead of the final particulate filter, particulate filtration at MERV 14 or greater per ASHRAE 52.2, pressure-drop measurement, and baseline gaseous pollutant testing with passive monitors followed by mitigation and re-monitoring where limits are exceeded.
One vocabulary caution before you write filtration requirements. On the equipment side the correct terms are gas-phase filtration, molecular filtration, acid removal, and corrosion control — not "deacidification", which in conservation literature names the treatment of acidic paper and objects by adding alkaline compounds and is not something an air-treatment unit does. Note the scope boundary in ISO 10121-3:2022 as well: it classifies gas-phase air cleaning devices supplying single-pass outdoor air and explicitly does not apply to recirculating units or to pollution from indoor sources — which is exactly the situation in a stack area, where the acids come from the collections and the shelving. Device-level evidence for an in-room recirculating cabinet belongs under ISO 10121-2 or ASHRAE 145.2, with media-level evidence under ISO 10121-1 or ASHRAE 145.1.
8. Fire Protection, Shelving, and Building Requirements
Fire Protection
ISO 11799 requires automatic fire detection (smoke detectors in all storage areas, connected to a monitored alarm system) and recommends water-based suppression (sprinklers) over gas-based systems for paper collections — counterintuitively, water damage from sprinklers is more recoverable than the total loss from an unsuppressed fire. For areas with irreplaceable materials, water mist systems offer a compromise with less collateral water damage.
Shelving and Storage Equipment
- Shelving must be made of powder-coated steel or stainless steel — not uncoated wood, which off-gasses organic acids
- Bottom shelves must be minimum 150mm above floor level (flood protection)
- Aisles between shelving units must be minimum 800mm for accessibility and air circulation
- Storage boxes and folders should conform to ISO 9706 (permanent paper) or ISO 11108 (archival paper) standards
Building Envelope
The standard specifies that the building envelope must be designed to minimize uncontrolled air infiltration. In practice:
- Vapor barriers in walls and foundations (especially in humid climates)
- Vestibules or airlocks at all external entrances to collection storage areas
- Door sweeps and gaskets on all doors between conditioned and unconditioned spaces
- Windows in collection storage areas should be eliminated or permanently sealed and insulated
9. How to Demonstrate Compliance
Since there is no formal ISO 11799 certification process, compliance is demonstrated through documentation and monitoring data:
- Environmental monitoring records: Continuous temperature and RH data from calibrated sensors, with documented review of excursions outside acceptable ranges
- Air quality testing: Periodic measurement of particulate counts and gaseous pollutant concentrations, with results compared to the standard's thresholds
- Building documentation: Fire system inspection records, pest management logs, disaster response plan documentation
- Equipment specifications: Dehumidifier/HVAC specifications demonstrating capacity to maintain required ranges under worst-case seasonal conditions
For facilities seeking funding or accreditation, ISO 11799 compliance documentation is often a prerequisite. The standard provides the framework; your monitoring data proves you're meeting it.
ISO 11799:2024 gives the monitoring side a numbered home: clause 8, "Environmental monitoring", with 8.2.3 "Deployment and sample rates" and 8.2.4 "Data retention and analysis". EN 16893:2018 parallels it with an environmental strategy (4.3) and an environmental monitoring strategy (4.4), air quality in 5.4 and mechanical control in 5.5.2. Practically, that means defining the measurement interval and averaging window for every limit you write, so that "±5% RH" cannot be argued about after handover: log continuously and analyze trend as well as instantaneous value, monitor gas-phase pollutants rather than temperature and RH alone, and check sensor placement against the actual storage envelope — a wall sensor near a door does not describe conditions inside closed compact shelving.
One caution on secondary summaries. A national archivists' association article describes the 2024 revision as mandating continuous monitoring with trend analysis and a 30-year systems-modernization cycle. Those specifics have not been verified against the standard text, so they should not be quoted as requirements until you have the clause in front of you.
10. What to Ask a Supplier Before You Write Them Into the Specification
Most failed archive climate projects fail on the specification, not on the equipment. Put these questions into the tender and require written answers — a supplier who cannot answer them cannot be held to a number later.
- Which edition and which annex? ISO 11799:2015 or 2024, EN 16893:2018, BS 4971:2017, NARA 1571 with Supplement 2 as effective 17 January 2023 — and for every quoted value, is it normative or from an informative annex?
- What is the time basis of any "±" figure? Short-term, seasonal, or per 24 hours, and measured over what averaging window? If the supplier cannot say, the number is not usable in a contract.
- What control band can the unit actually hold — short-term and seasonal stated separately — at which measurement point, and at what maximum rate of change? Ask for the band, not the set point.
- Humidity control capability. Separate dehumidification and humidification, the water source and its treatment (reverse osmosis or deionized water for dissolved salts), and failsafe behavior if RH approaches the upper limit. NARA 1571 requires units serving holdings areas to be designed for both dehumidification and humidification, with a failsafe humidistat downstream of the filtration system.
- Performance evidence, with test conditions. Which method — ISO 10121-2, ISO 10121-1, ASHRAE 145.2, ASHRAE 145.1, or equivalent — at what challenge gas, concentration, airflow, and residence time? Remember that ISO 10121-3 does not cover recirculating in-room units, and that ASHRAE states it does not certify or approve products: "tested per ASHRAE 145.x" is a laboratory rating, not an approval.
- Report integrity and laboratory accreditation. Which laboratory issued the report, under what accreditation (ISO/IEC 17025, and whether the body is a signatory to the ILAC mutual recognition arrangement), does the test item appear in that laboratory's accredited scope or carry a disclaimer, and is the report signed by an authorized signatory within their competence?
- Media specification and service life. Media type and mass, predicted breakthrough point, replacement interval, how performance is monitored in service, and how spent media is disposed of.
- BMS integration, data, and deployment cost. Protocol (for example RS485/Modbus), point list, alarm handling, logging interval, data retention and trend export — plus whether the design requires ductwork or air handling unit downtime, or whether rooms can be commissioned individually and the equipment relocated later.
Two rules keep the resulting specification honest. Requirements should be set by the storage envelope — your room dimensions, target band, permitted fluctuation, and pollutant thresholds — not by a product's headline capacity. And every figure you keep should name the document it came from, because "ISO 11799 compliant" on its own guarantees no measurable condition at all.
Equipment That Meets ISO 11799 Standards
The CJS-HP100B is designed for ISO 11799-compliant archive environments: ±3% RH control, against the ±5% band that specifications normally allow, H12 HEPA filtration, 99.90% acid gas removal (SO2, NO2, TVOC all ≥99.9%), ≤48 dB(A) for quiet operation, and IoT data logging for compliance documentation. CE and SDS certified. Deployed in national and municipal archives.
View CJS-HP100B Specifications →Visit our online store for pricing →
Questions? alex@syprointl.com | +86 177 1055 7225
By environment: Archive & vault · Museum storage · Library special collections · Film & AV archive